Commercial Exhaust Hood Types: Type I, Type II and Styles

10 min read
Wall canopy exhaust hood over commercial cookline

Commercial Exhaust Hood Types: Type I, Type II and Styles

Wall canopy exhaust hood over commercial cookline

A commercial exhaust hood is chosen in two steps. First you pick the type by what your equipment gives off: grease and smoke call for a Type I hood, steam and heat for a Type II. Then you pick the style by how your line is laid out: wall canopy, island canopy, backshelf, eyebrow or pass-over. Size, airflow and construction follow from those two choices. We build custom stainless steel exhaust hoods in Brooksville, Florida, and this guide walks through the decisions in the order you will face them.

Day-metal
Custom Hoods Made for Your Kitchen
DAY METAL builds custom stainless steel exhaust hoods in Brooksville, tailored to commercial kitchen layouts and made with precision CNC fabrication.
Visit

TL;DR

  • Type I hoods handle grease and smoke over fryers, ranges, griddles and broilers. Type II hoods handle steam and heat over dishwashers and steam tables.
  • Style is set by layout: wall canopy, single or double island canopy, backshelf, eyebrow or pass-over.
  • The code baseline is a 6-inch overhang beyond the appliance edge on open sides and a canopy no more than 4 feet above the cooking surface. Exposed flame sets the lowest edge height.
  • Exhaust airflow is set by duty level and hood style, and the heaviest appliance under a hood governs the whole hood.
  • Stainless steel is the standard material for grease-contact surfaces, and a custom-built hood can be sized to your exact line.

Table of Contents

Type I and Type II: the first decision

Commercial hoods fall into two broad categories: Type I for collecting and removing grease and smoke, and Type II for steam, water vapor, heat and odors where grease is not present.

Type I hoods always include filters or baffles. They are normally required over fryers, ranges, griddles, broilers, ovens and steam-jacketed kettles. The ICC’s training material adds that Type I hoods require fire suppression.

Type II hoods remove steam, vapor and heat, may lack grease filters, and are typically used over dishwashers and steam tables.

Appliance lists vary slightly by jurisdiction. The City of Tucson’s IMC-based chart puts deep-fat, kettle, donut and pressure fryers, griddles, open-burner ranges, under-fired broilers and salamanders under Type I, and steamers, steam-jacketed kettles and standard ovens under Type II. It lists cheesemelters, coffee makers, counter-top toasters and steam tables as needing no hood. Your local plan reviewer has the final word on each appliance.

Type I and Type II hood comparison

Gauge requirements

The ICC material lists No. 18 gage steel or No. 20 gage stainless steel for Type I hoods, and No. 22 gage steel or No. 24 gage stainless steel for Type II. New York City’s code uses the same thicknesses, for example stainless not less than 0.0335 inch for Type I. Stainless is what we fabricate hoods from.

Hood styles and where each belongs

The style decision is about where your equipment sits and how air moves around it. Katom’s buyers’ guide describes six common styles:

Style Where it fits Watch for
Wall-mounted canopy Any equipment placed against a wall The wall acts as a back panel and improves capture
Single-island canopy One line of freestanding equipment Needs more airflow than a wall canopy of equal size
Double-island canopy Back-to-back island lines Behaves like two wall canopies but is more exposed to cross drafts
Backshelf Counter-height equipment, low ceilings Not for high-exhaust equipment such as charbroilers
Eyebrow Mounts on ovens and dishwashers Can run only when the door is open
Pass-over Low over counter-height equipment so plates pass over Not suited to the heaviest duty

The ICC notes that cuisine, production rates, traffic patterns, staff preference and the room’s configuration all influence the choice. Two kitchens with identical equipment can reasonably end up with different hoods.

The airflow penalty for island placement is real. The CKV Design Guide explains that for the same heat plume, a single-island canopy needs more exhaust than a wall canopy, which needs more than a proximity (backshelf) hood. If your floor plan allows the line to sit against a wall, that is usually the efficient layout.

Matching hood type to your cooking line

Work through your equipment list appliance by appliance:

  1. Grease or smoke producers (fryers, griddles, ranges, charbroilers): Type I.
  2. Steam and heat only (dishwashers, steamers, steam tables): Type II, or no mechanical exhaust for some equipment.
  3. Mixed lines: the heaviest-duty appliance under a hood sets the exhaust rate for the whole hood, so grouping similar appliances together can keep the hood and fan smaller.

Alameda County’s design guideline classifies cheesemelters and tilting skillets as light-duty Type I appliances. It also notes that chemical-sanitizing and undercounter dishwashers typically need no mechanical exhaust, though room size, ceiling height and other heat sources still count.

If you are specifying a hood alongside prep tables, sinks and wall cladding, think of the kitchen as one stainless package. Our guide to hotel kitchen design covers how layout and flow affect fixture placement.

Commercial kitchen hood dimensions

Hood size starts from the equipment beneath it, not from a catalog.

Overhang. Under the model code as adopted in New York City, the inside lower edge of a canopy hood must extend at least 6 inches beyond the edge of the appliance on all open sides. The front lower lip may be no more than 4 feet above the cooking surface. Non-canopy hoods must sit no more than 3 feet above the cooking surface. The SYNC construction standard uses 12 inches as the default overhang for typical wall-canopy installations, with 6 inches as the code minimum.

Height above equipment. According to the ICC’s guidance, the lowest hood edge must be 6 inches above cooking surfaces without exposed flame, 24 inches above exposed flame or burners, and 30 inches above charcoal or charbroil equipment.

Lower is better. SYNC notes that raising the hood enlarges the capture area and increases the required exhaust rate, so hoods should be mounted as low as the listing and duty allow.

Length. Measure the full cooking line, then add the overhang at each open end. One local checklist, from the Crawfordsville Fire Department, also limits each exhaust outlet to serving no more than 12 feet of hood, which affects how long runs are divided.

Example: a wall-mounted line of a 36-inch range and a 24-inch fryer is 60 inches wide. With a 6-inch minimum overhang at each open end, the canopy is at least 72 inches wide. With the 12-inch default, it is 84 inches.

Commercial kitchen hood dimensions

Exhaust hood sizing: airflow and make-up air

Airflow is expressed in cubic feet per minute per linear foot (cfm/ft) and depends on duty and style. Minimum rates for unlisted hoods from the CKV Design Guide:

Style Light Medium Heavy Extra heavy
Wall canopy 200 300 400 550
Single island 400 500 600 700
Double island 250 300 400 550
Backshelf/pass-over 250 300 400 Not allowed
Eyebrow 250 250 Not allowed Not allowed

These are model-code minimums, and local amendments differ. Hoods tested to UL 710 and listed can generally run at lower rates than unlisted hoods, according to the California Energy Commission guide. Lower rates can also be substantiated through ASTM F1704 testing of a specific hood and appliance lineup, which is called custom engineering a hood. Lower airflow means a smaller fan and less conditioned air to replace.

That replacement air is make-up air. Exhausting without supplying it creates negative pressure and weakens capture. Examples of how states handle it:

For a Florida kitchen, confirm requirements with your local building and fire officials before drawings are finalized.

Materials, construction and the fire code

NFPA 96 is the Standard for Ventilation Control and Fire Protection of Commercial Cooking Operations. The 2024 edition took effect May 13, 2023, and its Chapter 5 covers hood construction and size.

The SYNC standard specifies stainless steel or galvanized bodies, with exposed and grease-contact interior surfaces in stainless finished to NSF/ANSI 2 for cleanability. Options include 304 or 430 stainless. The Crawfordsville checklist asks for external joints welded and sealed grease-tight on Type I hoods, and watertight joints on Type II.

That makes welding quality part of hood quality. Our write-up on sheet metal welding for commercial kitchens explains what to look for in seams. Grease filtration matters just as much, and we cover it in hood baffle filter options.

Fire risk is also an insurance matter. French restaurant insurer Spoon’s guide to kitchen hood fires covers prevention and response, and a properly built, cleanable hood is the first line of prevention.

What a commercial hood costs

Prices vary widely because hoods are sized to each line. EquipLane illustrates hood bodies from about $2,500 for a Type II hood to $18,000 for a large island canopy, with a full installed ventilation package near $35,000. Cooking-line length, hood style, duct run, the condition of the space and local codes drive the number. Budget the hood as a share of total fit-out rather than a fixed figure, since it scales with the project.

Perspective

Most hood problems we see discussed come back to one thing: a hood bought off a catalog for a line that does not match it. A standard size forces compromises in overhang, height or length, and those are exactly the dimensions that decide capture.

That is why we build to the line. DAY METAL manufactures every product locally in Brooksville, Florida, using CNC technology and custom engineering, with a personalized approach so each solution matches the client’s requirements. Our team brings over 60 years of combined experience to stainless fabrication.

For architects and contractors, a custom hood means one fabricator can coordinate the hood with the countertops, tables, sinks and wall cladding around it, all in the same stainless.

the author

Get a hood built for your line

DAY METAL makes custom commercial exhaust hoods, along with countertops, premium sinks, wall cladding, stainless tables and heavy metal enclosures, for restaurants, hotels, healthcare and education. Send us your equipment list and layout and we will work from there. See our full range or our custom fabrication and welding page.

Day-metal

FAQ

What is the difference between Type I and Type II hoods?

Type I hoods remove grease and smoke and include filters or baffles. They go over fryers, griddles, ranges and broilers. Type II hoods remove steam, heat and odors where grease is absent, and are typical over dishwashers and steam tables.

What is the NFPA code for commercial kitchen hoods?

NFPA 96 governs ventilation control and fire protection for commercial cooking. Its 2024 edition took effect May 13, 2023, and Chapter 5 covers hood construction and size. Your local authority decides which edition applies.

How far should a hood overhang the equipment?

The model code minimum is 6 inches beyond the appliance edge on all open sides, with the canopy no more than 4 feet above the cooking surface. Many installations default to 12 inches for wall canopies.

What are stainless steel commercial hoods made from?

Common options are 304 or 430 stainless steel, with grease-contact surfaces finished for cleanability to NSF/ANSI 2. Type I hoods call for No. 20 gage stainless or thicker.

Sources